Analog Inputs 750-456
:$*2Ç,2 Ç6<67(0
2
Technical Data:
Item Number 750- 456, 456/000-001
Number of channels 2
Nominal voltage via system voltage (DC DC converter)
Current consumption
(internal)
65 mA
Overvoltage protection 35 V max.
Signal voltage +/- 10 V
Resistance
570 k
Resolution 12 Bit
Isolation 500 V System/Power supply
Conversion time 2 ms typ.
Bit width per channel 16 Bit Data, 8 Bit Control/Status
Operating temperature 0°C....+55°C
Configuration none, optional via software parameter
Wire connection CAGE CLAMP; 0.08 to 2.5mm
2
Dimensions
(mm)WxHxL
12 x 64* x 100 (*from upper edge of the carrier rail)
Attention:
The value of the input signal should be in a range of 0V to 10V or even no signal.