8644 WAGO I/O
System 750
p. 12/19
Electronic modules series 750 WAGO
Fieldbus modules (others on request)
Profibus DP/FMS – EN 51070; 12 MBaud; digital and analog signals
Technical Data
Voltage supply
24 V/DC
(+20%/-15%)
Internal current
500 mA at 24 V
Insulation
500 V system/supply
Power contacts, current
10 A DC max.
Rating
IP20
Temperatures
Operating
Storage
32°F up to 131°F
(0°C up to +55°C)
-4°F up to 140°F (-20°C up to +60°C)
Relative humidity
95% max, not condensating
Conguration of eldbus module
Via PC or PLC device
Current consumption
(eldbus modules)
350 mA
(internal)
Wire connection
CAGE CLAMP
®
AWG 28-14
(0.08 mm
2
–2.5 mm
2
)
Vibration resistivity
Acc. to IEC 60068-2-6
Shock resistivity
Acc. to IEC 60068-2-27
Certications
UL
E175199
Dimensions
Fieldbus modules
I/O modules
W x H x L
51 x 65 x 100 mm
12 x 64 x 100 mm
This eldbus module allows
connection of the AirLINE Sys-
tem as a slave to a PROFIBUS
eldbus.
The eldbus module is capable
of supporting all bus modules
and automatically creates the
local process image which
may include analog and digital
modules.
Max. no. of nodes
96 with repeater
Max. no. I/O points
Approx. 6000
(depends on Master)
Transmission medium
Cu cable acc. to EN 50170
Max. length of bus line
100 m –1200 m
(depends on Baud rate on the cable)
Baud rate
9.6 kBaud – 12 MBaud
Transmission time typ.
Approx. 1.0 ms
(10 nodes; 32 Is, 32 Os per node; with 12
MBaud and digital signals)
Fieldbus module connection
1 x D-SUB 9; plug with shielding
Max. I/O modules per node
64
Digital points per node
256 Is or Os
Analog points per node
64 Is or Os
Current supply
105 mA typ. 900 mA max.
Factory preset
DP/FMS dual operation 32
analogue points per node max.
(inputs and outputs)
InterBus – EN 50254; digital and analog signals
This eldbus module allows
connection of the AirLINE System
as a slave to an INTERBUS
eldbus.
The eldbus module is capable of
supporting all bus modules and
automatically creates the local
process image which may include
analog and digital modules.
Max. no. of nodes
256
Max. no. I/O points
4096
(depends on Master)
Transmission medium
Certied Cu cable
Max. distance between
nodes
400 m
Baud rate
500 kBaud
Transmission time typ.
1.43 ms
(10 nodes; 32 ls, 32 Osper node)
Fieldbus module connection
2 x D-SUB 9; plug with shielding
Max. I/O modules per node
64
Digital points per node
256 Is or Os max.
Analog points per node
32 Is or Os max.
Current supply
105 mA typ. 900 mA max.